Technical Guide
GPM to LPS Conversion Factor for Philippine Pump Specs
The GPM to LPS conversion factor is 0.0630902: multiply US gallons per minute by 0.0630902 to get litres per second, or divide GPM by 16 for a fast field estimate accurate to about 0.9 percent. Philippine pump specs mix GPM, LPS, and m3/hr because equipment comes from an ISO 9001 certified partner factory alongside metric national codes, and a US gallon differs from an Imperial gallon by 20 percent, so verify the standard before ordering.
GPM to LPS conversion formula and quick reference table
The GPM to LPS conversion uses one constant: to convert US gallons per minute to litres per second, multiply GPM by 0.06309. To go the other way, multiply LPS by 15.85. The exact constant is one US gallon equals 3.785411784 litres, divided by 60 seconds, so 1 GPM equals 0.0630902 L/s. For field work the usable shortcut is: divide GPM by 16 to get LPS, multiply LPS by 16 to get GPM.
That approximation runs about 0.9 percent low, which is well inside the tolerance of any pump curve you will actually buy against. Philippine specifications frequently need a third unit, cubic metres per hour, because most metric-standard overseas pump catalogs publish duty points that way. The bridges are: 1 L/s equals 3.6 m3/hr, and 1 GPM equals 0.2271 m3/hr. Print the GPM to LPS table below and keep it next to the drawings, because you will convert the same duty point three or four times between design and delivery.
| US GPM | LPS (L/s) | m3/hr |
|---|---|---|
| 10 | 0.63 | 2.27 |
| 25 | 1.58 | 5.68 |
| 50 | 3.15 | 11.36 |
| 75 | 4.73 | 17.03 |
| 100 | 6.31 | 22.71 |
| 150 | 9.46 | 34.07 |
| 200 | 12.62 | 45.42 |
| 250 | 15.77 | 56.78 |
| 300 | 18.93 | 68.14 |
| 400 | 25.24 | 90.85 |
| 500 | 31.55 | 113.56 |
| 750 | 47.32 | 170.34 |
| 1,000 | 63.09 | 227.12 |
US gallons or Imperial gallons: the conversion error nobody catches
The single most expensive mistake in this conversion is not the arithmetic, it is the gallon. A US gallon is 3.7854 litres. An Imperial gallon is 4.5461 litres. The Imperial gallon is 20.1 percent larger, so 1 Imperial GPM equals 0.07577 L/s while 1 US GPM equals 0.06309 L/s. Convert 200 GPM using the wrong gallon and you are off by 2.5 L/s, which is enough to move you a full frame size on a multistage pump or push a duplex set into triplex territory. In practice, Philippine plumbing design leans US: the National Standard Plumbing Code methodology descends from the US model codes, Hunter's Curve tables are published in US GPM, and most consultant drawings issued in Metro Manila follow that convention. Imperial GPM shows up when equipment or documentation traces back to UK, Australian, or older British Commonwealth sources, and it shows up on legacy nameplates. The rule we apply on every RFQ: if a flow figure is written as GPM with no qualifier on a Philippine plumbing drawing, treat it as US GPM, then confirm in writing before anything is ordered. Confirming costs one email. Discovering it after a 45 to 90 day made to order lead time costs a project schedule.
Why Philippine pump specs mix GPM, LPS, and m3/hr
Commercial and industrial pump equipment supplied in the Philippines is sourced from a mix of ISO 9001 certified partner factories and vetted overseas manufacturers, and each manufacturer's home market has its own default flow unit. US influenced catalogs default to GPM and PSI. Metric standard catalogs default to LPS or m3/hr and bar or metres of head. A single project can end up with a booster pump curve in GPM and PSI, a fire pump reference in LPS, and a VFD panel programmed in m3/hr, all describing the same building's water system. National Structural and Plumbing Code and National Building Code sizing calculations in the Philippines are typically worked in metric units, which means a GPM rated datasheet has to be converted before it can be checked against a code based demand calculation. The discipline that prevents errors is to fix one master unit per project, usually L/s because it converts cleanly to both sides (multiply by 15.85 for GPM, multiply by 3.6 for m3/hr), and to write every flow figure on the submittal with its unit spelled out. When JOHOB Hardware Trading reviews an RFQ, we restate the duty in all three units on the quotation so the consultant, the contractor, and the factory are reading the same pump from our pumping and pressure systems range.
Convert the head too: PSI, bar, and metres of water column
A flow conversion alone will not let you select a pump. A duty point is flow plus head, and head units get mixed exactly the same way. The relationships you need: 1 bar equals 10.2 metres of water column, 1 bar equals 14.5 psi, and 1 psi equals 0.703 metres of water column. So a specification calling for 40 psi at the outlet is 28.1 metres of head, and 3 bar is 30.6 metres. Manufacturer curves for the pumps we supply are plotted with head in metres on the vertical axis and flow in m3/hr on the horizontal axis, which is why both conversions have to happen before you can read a curve at all. Two cautions. First, psi at a fixture is residual pressure, not total pump head: total head must add static lift from the tank or suction source, plus friction losses through the riser and fittings. Second, gauge pressure and absolute pressure differ by roughly 1 bar, so confirm which one a metric datasheet is quoting. If you are working from tank level and building height rather than from a stated head, our guide on how to size a booster pump for a commercial building walks through the head build up step by step, including static, residual, and friction components.
Worked example: converting a duty point before you order
Here is the arithmetic end to end, using an illustrative duty point rather than a project reference. Suppose a consultant drawing specifies 195 GPM at 40 psi residual for a commercial building booster set. Step one, the GPM to LPS conversion: 195 GPM multiplied by 0.06309 equals 12.3 L/s. Step two, convert to catalog units: 12.3 L/s multiplied by 3.6 equals 44.3 m3/hr, or equivalently 195 multiplied by 0.2271 equals 44.3 m3/hr. Step three, head: 40 psi multiplied by 0.703 equals 28.1 metres, before adding static lift and friction losses, so the true selection head will be higher. Step four, read the curve: you now look for a pump family that covers roughly 45 m3/hr at your final calculated head, and you check that the duty point sits near the best efficiency point rather than at the far right end of the curve. Step five, configuration: a duty of this size is normally handled as a duplex or triplex set from our commercial booster pumps range rather than a single pump, so the per pump flow is the total divided across the running units, with one unit on standby. The standby unit does not change the total flow conversion, only the individual pump selection. Convert first, then select, then decide configuration. Doing it in the other order is how oversized motors get ordered, and our guide on when a VFD is worth it versus a fixed speed pump covers the control side of the same decision.
Getting a pump quoted in the units you specified
JOHOB Hardware Trading is a Philippines based industrial equipment supplier serving commercial, industrial, and institutional buyers, with nationwide coverage across NCR, Luzon, Visayas, Mindanao, and the PEZA, SBMA, and Clark zones. Equipment is sourced from ISO 9001 certified partner factories and vetted overseas manufacturers, with CE marking on electrical components and ASME compliance on pressure vessels where applicable, and delivered with local warranty and after sales support. For pumping and pressure systems that means booster, transfer, and submersible pumps, VFD duplex control panels from our VFD and control panel options, and the piping, valves, and stainless steel flexible hose that go with them. To convert your duty point and return a selection, send us the flow with its unit stated (GPM, LPS, or m3/hr), the required head or residual pressure with its unit, the static lift from tank or source to the highest fixture, the building type, and the power supply available. We respond to RFQs within one business day. Pricing is quote based and not published, 12 percent VAT applies to VAT registered buyers, and PEZA and SBMA locators and exporters are zero rated. Standard lead times run 21 to 35 days ex stock and 45 to 90 days for made to order configurations, so converting units correctly at the RFQ stage is what keeps that clock from restarting. Process duties like commercial laundry water requirements in the Philippines get the same three unit restatement on the quotation.
Frequently Asked Questions
What is the exact GPM to LPS conversion factor?
1 US gallon per minute (GPM) equals 0.0630902 litres per second (LPS). This comes from 1 US gallon equaling 3.785411784 litres, divided by 60 seconds. To convert LPS to GPM, multiply by 15.85. For a fast field estimate, divide GPM by 16 to get LPS, though the exact factor should be used for a final pump duty-point specification, not the rounded shortcut.
Is a US gallon the same as an Imperial gallon for pump conversions?
No. A US gallon is 3.785411784 litres, while an Imperial gallon is 4.54609 litres, about 20 percent larger. If a pump datasheet does not state which gallon it uses and the wrong one is assumed, the converted LPS or m3/hr figure will be off by roughly 20 percent, which can lead to an undersized or oversized pump order. Check for a metric cross-reference on the datasheet, or ask the supplier directly which standard the curve was built on.
How do I convert GPM and PSI together to a metric pump duty point?
Convert flow with GPM multiplied by 0.06309 to get LPS, and convert head with PSI multiplied by 0.0689476 to get bar, or PSI multiplied by 0.7031 to get metres of water column. Both conversions are needed together, since a pump curve is read at the intersection of flow and head. Converting only the flow side or only the pressure side leaves the duty point unable to be checked against a metric-rated curve.
Why do Philippine pump datasheets show different units for the same pump?
Pumping equipment supplied in the Philippines is sourced from a mix of ISO 9001 certified partner factories and vetted overseas manufacturers, each defaulting to their home market's unit system: GPM and PSI, or LPS, m3/hr, and bar. A single project can end up with pump, fire system, and VFD panel documentation in three different unit systems for the same building, while Philippine code based sizing under the National Structural and Plumbing Code and the National Building Code is typically worked in metric units, so a conversion step is usually needed before comparing a datasheet to a project spec.
Does JOHOB Hardware Trading quote pumps in GPM or LPS?
Either. JOHOB Hardware Trading supplies booster, transfer, and submersible pumping and pressure systems, including VFD duplex panel setups, nationwide across the Philippines. A duty point submitted in GPM, LPS, m3/hr, PSI, or bar is converted and cross-checked against the manufacturer's curve before a quote is issued. Pricing is quote based, RFQs get a response within one business day, and standard lead times run 21 to 35 days ex stock or 45 to 90 days for made to order configurations.
Related Pages
- Guide: How to Size a Booster Pump
- Pumping and Pressure Systems
- Commercial Booster Pumps
- Guide: VFD vs Fixed-Speed Pumps
- Guide: Commercial Laundry Water Requirements
- Electrical Panels and Controls
- Water Storage Tanks
Reviewed: August 2026
Found this useful? Add Johob as a Preferred Source on Google so our supply guides show up first next time you search.
Talk to Us About Your Project
Send us your requirements and we'll return a written recommendation within 3 to 5 business days. Response within 1 business day.
Request a Quotesales@johob.com · +63 997 078 9953 (Viber)